Home > Buy Now > RPV Electro Technology Phils. Corp. > Motor Management System
 


RPV Electro Technology Phils. Corp.
 
icon Energy (Kwh) & Multifunction Meter
icon Power Quality Meter & Analyzer ( Fix & Portable )
icon Generator Controls, Monitoring & Protection
icon Automatic Transfer Switch (ATS)
icon Protective Relaying
icon Motor Protection Relays
icon Data Logging Instruments
icon Test & Measuring Instruments
icon Energy Saving Device & Equipment
icon Energy Efficient Transformers
icon Soft Starter & VSD
icon Power Quality Solutions
icon Surge Protection Device or TVSS
icon Automatic Voltage Regulator (AVR) & UPS
icon Harmonic Filters & Reactors
icon Power Dip Ride Thru
icon Energy Managent System
icon Energy Billing System
icon Demand Management System
icon Synchronizing System
icon Motor Management System
icon Engineering Services
icon Power Quality Tips
icon Energy Saving Tips

line

icon Company Profile
icon Buying Leads
icon Index
icon Guest Book

line



visitors: 20336
 
Contact us
RPV Electro Technology Phils. Corp.
[Phillippines]
Address:
G/F Mamikas Bldg. Riverside Drive Ortigas Ext. Sta. Lucia Pasig City Metro Manila 1600 Phillippines
Phone:
63-2-9161984
Contact name:
Roland Vasquez , CEO
Inquire now










RPV Electro Technology Phils. Corp.



 
Motor Management System

 

Model 777

The Model 777 Product Line includes a wide selection of options which are designed for a wide variety of applications. Model 777 products are UL listed, CSA recognized and CE approved. They combine overload, underload, and voltage and power monitoring functions in one package. They also provide a 3-digit display for viewing voltage, current, power and last fault information to simplify diagnostics.

The Model 777 units are designed to best handle loads ranging from 1-800A, provide linear trip capability, handle medium voltage applications, and provide underpower trip capability for special pumping applications.

Adding the optional RS485MS-2W communications module enables modbus RTU communications over an RS-485 bus. The Model 777 can then communicate with SymCom's RM-1000 and RM-2000 remote displays as well as SymCom's Solutions software running on an IBM compatible PC. The Model 777 can communicate with other Modbus master devices such as PLCs, RTUs, SCADA systems, DCS systems and others.

Spec Sheet

Installation Guide

Specifications
Input Voltage 200-480VAC, 3Ø (Standard)
(500-600VAC, 3Ø Available)
Frequency 50 or 60Hz
Motor Full Load amp Range 2-90 Amps, 3Ø (Direct)
91-800 Amps, 3Ø (External CT's)
Programmable Operating Points
LV - Low Voltage Threshold * 170V (450V*) - HV Setting
HV - High Voltage Threshold * LV Setting - 528V (660V*)
VUB - Voltage Unbalance Threshold 2-15% or 999 = Off
MULT - # of Loops or CT Ratio (XXX:5) 1-10 Loops or 100-800 Ratio
OC - Over Current Threshold (20-100A) / MULT
UC - Under Current Threshold (0, 10-98A) / MULT
CUB - Current Unbalance Threshold 2-25% or 999 (OFF)
TC - Over Current Trip Class ** 5, J5, 10, J10, 15,
J15, 20, J20, 30, J30
RD1 - Rapid Cycle Timer 0-500 Seconds
RD2 - Restart Delay After All Faults Except Under Current (Motor Cool Down Timer) 2-500 Minutes
RD3 - Restart Delay After Under Current (Dry Well Recovery Timer) 2-500 Minutes
#RU - Number of Restarts After Under Current 0, 1, 2, 3, 4, A (Automatic)
ADDR - RS485 Address A01-A99
#RF - Number of Restarts After All Faults Except Under Current *** 0, 1, oc1, 2, oc2, 3,
oc3, 4, oc4, A, ocA
UCTD - Under Current Trip Delay 2-60 Seconds
GF - Ground Fault Current Threshold (3-20A) / MULT or OFF
Specifications
Low Voltage 4 seconds
Output Contact Rating
(Pilot Duty) SPDT
480VA @ 240VAC
Transient Protection (Internal) 2500 V for 10 mSeconds
Accuracy
Voltage ±1%
Current ±3% ( <100 amps direct)
Timing 5% ±1 Second
Repeatability
Voltage ±0.5%
Current ±1% ( <100 amps direct)
Temperature Range 0 to 70°C
Physical Specifications
Dimensions 3.0" H x 5.1" D x 3.6" W
Power Consumption 10 Watts (Max.)
Weight 1.2 lbs.
NOTES: SymCom's 777-LR & 777-MV can be programmed prior to installation by applying 115 VAC between the L1 and L2 terminals.
* 575 volt Model (MS 777-575)
** If J prefix is displayed in trip class setting, jam protection is enabled.
*** If "oc" is enabled in the #RF setting, the Over Current will be included as a normal fault and the relay will automatically restart after RD2 expires, otherwise, manual reset is required after an Over Current Fault.

MOTOR MANAGEMENT SOFTWARE

 

The Model

Solutions Software allows an IBM PC compatible computer to communicate with an RM-2000, RM-1000, Model 777, Model 77C or Model 601 connected to an RS-485 network using Modbus protocol. The program allows an operator to easily view the 3-phase voltages and currents, as well as key operating parameters such as: average voltage, average current, voltage unbalance, current unbalance, power factor, kW and remaining restart delay times. The software allows programmable limits to be viewed and modified from a single screen. In addition, the operator can start and stop (up to 99) individual Model 777s, Model 77Cs or Model 601s connected to the RS-485 network and log data to a file for future analysis.

 

Model RM-2000

The RM-2000 is a motor monitoring device to be used in conjunction with SymCom's Model 777. The RM-2000/777 motor management system combines unsurpassed electronic motor protection and critical, user-friendly motor monitoring.

The RM-2000 has membrane keypad controls which allow both monitoring and control of a 777 MotorSaver® through a RS-485 network using Modbus RTU protocol. A second communication port is standard and allows monitoring and control of up to 99 RM-2000 devices from a PLC, DCS, or SCADA system or a PC with Solutions software installed . The RM-2000 is environmentally protected and is easily mounted on the front of a panel or MCC.

 

 