TECHNICAL SPECIFICATIONS
General
This specification describes the features and design of the Power Purifier. Each system design
ensures maximum reliability, serviceability and performance. The Industrial Power Purification System
receives extremely polluted, raw electrical power and purifies it for use by sensitive electronic equipment.
Wherever noise free, isolated, steady voltage is required; use the Industrial Power Purification System.
Standards
Power Purifiers designed in accordance with:
Institute of Electrical and Electronic Engineers (IEEE C62.41-1991)
National Fire Protection Association (NFPA) 70, National Electric Code (NEC)
Underwriters Laboratories (UL) 1012 and 544 Listed
Safety
Underwriters Laboratories U/L 1012 -- U/L 544 -- CUL
Performance Specifications
Power Output 1?, 100% duty kva/kw, for linear and non-linear loads.
Line Voltage Regulation @ 100% load - + 2% Vout for +10% to -20% Vin.
@ 75% load - + 3% Vout for +10% to -35% Vin.
@ 50% load - + 3% Vout for +10% to -40% Vin.
@ 25% load - + 3% Vout for +10% to -45% Vin.
Immunity to Distortion @ 40%THD Vin, 5% THD Vout
Load Regulation + 2.5% for 0% to 100% load
Voltage Recovery 2 cycles to 95%, 3 cycles to 100%
K Factor K30 Rated
Power Factor Correction Input pf 0.95 typical
Harmonic Attenuation -23dB for load reflected harmonics
Galvanic Isolation NEC 250-5d, .001pf
Surge Protection Complies to U/L 1449 rating 330 v; ANSI/IEEE C62.41 Cat. B3
CMN Attenuation -140 dB
TMN Attenuation -120dB
Ride Through Capability 1 cycle
Reliability 200,000 hr. (MTBF)
Audible Noise 1 meter, A scale, 52dB to 56dB
Efficiency ?92%
Operating Temperature -20?C to +40?C.
TRANSFORMER CONSTRUCTION
Ferro resonant, copper coils, dry type, convection cooled, 600 volt class, 200?C system.
Core uses M-6 grade, grain oriented, stress relieved transformer steel.
Transformers are vacuum impregnated with epoxy resin.
Primary is multi-input voltage configured.
Input terminals are provided for source, conductors and ground.
Interface terminals are provided for output power hot, neutral and ground conductors.
All leads, wires and terminals are labeled to correspond with circuit wiring diagram.
Rating Nominal input voltage Single phase, 60 Hertz
250VA - 5KVA 120/208/240/480 VAC
8KVA - 25KVA 208/240/480VAC
*Note - 600VAC, single phase, 60 Hertz available upon request.
Rating Nominal output voltage Single phase, 60 Hertz
250VA 120
500VA - 25KVA 120/208/240VAC
Secondary configuration 240/120 split with 208 volt tap. 250va-120vac only.
CABINET CONSTRUCTION
NEMA type 1, general purpose, indoor enclosure.
Or NEMA type 2 indoor use, protected against falling non-corrosive liquids and dirt.
Heavy gauge steel. Base sub-structure adequate for fork lifting.
250VA - 3KVA are designed for panel or floor mounting.
5KVA - 25KVA floor mounting only.
WARRANTY 20 Years
Controlled Power warrants the core and coil of the Power Purifier against defective material or
workmanship for a period of 10 years form the date of purchase by the end-user, prorated for an
additional 10 years. Consumable and/or field replaceable items are warranted for 2 years.
|
|
|
|
| |
|
|
|