Home > Buy Now > Other Electrical Equipment > "EL Series" Centralized Emergency Lighting Inverter
 


RPV Electro Technology Phils. Corp.
 
icon Energy (Kwh) & Multifunction Meter
icon Power Quality Meter & Analyzer ( Fix & Portable )
icon Generator Controls, Monitoring & Protection
icon Automatic Transfer Switch (ATS)
icon Protective Relaying
icon Motor Protection Relays
icon Data Logging Instruments
icon Test & Measuring Instruments
icon Energy Saving Device & Equipment
icon Energy Efficient Transformers
icon Soft Starter & VSD
icon Power Quality Solutions
icon Surge Protection Device or TVSS
icon Automatic Voltage Regulator (AVR) & UPS
icon Harmonic Filters & Reactors
icon Power Dip Ride Thru
icon Energy Managent System
icon Energy Billing System
icon Demand Management System
icon Synchronizing System
icon Motor Management System
icon Engineering Services
icon Power Quality Tips
icon Energy Saving Tips

line

icon Company Profile
icon Buying Leads
icon Index
icon Guest Book

line



visitors: 21089
 
Contact us
RPV Electro Technology Phils. Corp.
[Phillippines]
Address:
G/F Mamikas Bldg. Riverside Drive Ortigas Ext. Sta. Lucia Pasig City Metro Manila 1600 Phillippines
Phone:
63-2-9161984
Contact name:
Roland Vasquez , CEO
Inquire now










RPV Electro Technology Phils. Corp.



 
Power Quality Solutions

"EL Series" Centralized Emergency Lighting Inverter

Inquire now

"EL Series" Centralized Emergency Lighting Inverter

Click to enlarge image

 Model Number EL Series
 Brand Name Controlled Power

 

Emergency Lighting Inverter System

EL-H SERIES

 5 Kwatt to 18Kwatt Specification

1.0 GENERAL

The emergency lighting inverter system is a single phase, continuous duty, seamless transfer inverter. 
The Series EL-H is designed to supply reliable, isolated, clean, regulated emergency power for emergency lighting and associated controls.  An efficient ferro-resonant transformer, microprocessor controlled solid state PWM inverter and long lasting battery pack provide immunity to all line disturbances and power interruptions with no break in AC output power.  Power factor correction and harmonic attenuation are provided.

 

The synchronous inverter produces a true uninterrupted output in any mode of operation.  A self-diagnostic monitoring alarm system continuously advises system status.


INVERTER RATINGS

EL 5000
EL 5400
EL 6000
EL 7000
EL 8000
5000 Watts
5400 Watts
6000 Watts
7000 Watts
8000 Watts
EL10K
EL12K
EL14.5K
EL15K
EL16K
EL18K
10 KWatts
12 KWatts
14.5 KWatts
15 KWatts
16 KWatts
16 kWatts

2.1 The maintenance bypass switch provides a means to repair and perform preventative maintenance without disruption of the load. The bypass switch is rated for the maximum Kva of the system.

3.0 STANDARDS
The systems shall be designed in accordance with:
American National Standards Institute (ANSI C57.110)
Institute of Electrical and Electronic Engineers (IEEE 519-1992 and IEEE C62.41-1991)
National Electric Code (NEC)
National Fire Protection Association (NFPA Article 70)
Underwriters Laboratories (U/L) 924,1449, 1778
FCC Article 15, Section J, Class A

3.1 Listings
The system shall be listed to U/L standards UL924 and UL1778

4.0 INPUT SPECIFICATIONS

4.1 Input Voltage: 120, 208 or 240 or 277 vac
4.2 Operating Range: +10% to -15%
4.3 Frequency Range: Capture 57.5 Hz to 62.5 Hz.
4.4 Power Factor: Self correcting to >0.95 (approaching unity)
4.5 Input Harmonics: < 5% THD (total harmonic distortion)

4.6 Spike Attenuation: 3000:1, exceeds ANSI/IEE C62.41 category B3 waveform

5.0 OUTPUT SPECIFICATIONS

5.1 Sine Wave Voltage: Maximum 3% harmonic distortion, any single harmonic.
5.2 Output Voltage: 20, 208/120, 240/120, 277/120
5.3 K Factor: 30 or better.
5.4 Power Factor: Unity rated.
5.5 Harmonic Attenuation: Reflected load generated harmonics are attenuated 23dB at the input.
5.6 Regulation: Typically better than +3%.

6.0 kVA RATINGS

6.1 Output is also rated for computer type loads with switch mode power supplies. Kva = Kwatt * / 0.7

7.0 BATTERY

7.1 Standard run times are 90 minutes at full Kwatt load. Additional run time up to 72 hours is available.
7.2 Type: Sealed, maintenance free, gas recombinant, self venting, suspended electrolyte with no gel contaminant.
7.3 Charger: Two stage, temperature compensated, matched to the system.
7.4 Recharge Time: Typically 24 hours to full charge.
7.5 Buss Voltage: Float 2.27 VPC, final 1.75 VPC. Factory tested with specific inverter before shipping.
7.6 Projected Life: 5 years service.

8.0 PERFORMANCE

8.1 Overload Capability: 125% for ten minutes.
8.2 Surge Capability: 150% of rated output without need of static bypass.
8.3 Frequency Stability: +0.2 Hz.
8.4 Inner Winding Capacitance: 0.01 pF (primary to secondary coupling).
8.5 Common Mode: 120 dB (106 : 1 ground noise attenuation).
8.6 Transverse Mode: 70 dB (3160 : 1 line noise attenuation).
8.7 Reactive Power Correction: Load at .6 pf corrected to > 0.95 at input (automatically self correcting).


9.0 DISPLAY MONITORS AND DIAGNOSTICS

9.1 DISPLAY
Auto Logging Analyzer 2020  ALA2020

9.2 ALARMS
Alarms the following faults:

  On Battery Power Low Battery
  Charger Failure On Bypass
  High temp  

10.0 COMMUNICATIONS INTERFACE

10.1 Status and alarm port. Used for remote annunciation
10.2 SNMP compatible

11.0 ENVIRONMENTAL

11.1 Isolation: NEC article 250-5d, complies with this standard that specifies a separately derived power source.
11.2 Operating Temperature: 0 (32) to 40 (105) degrees Celsius (F).
11.3 Storage Temperature: -20 to 50 degrees Celsius.
11.4 Relative Humidity: 95% non-condensed.
11.5 Elevation: 5,000 feet, 1500 meters.

12.0 MTBF

12.1 Total System: 100,000 hours MIL Spec standard 217E.
12.2 Transformer: 200,000 hours.
Mean Time to Repair: Less than one hour.

13.0 POWER DISTRIBUTION

13.1 Standard hard wired output 
13.2  Optional Normally -OFF bus or Timed Normally (OFF-ON) bus
13.3 Optional circuit breaker assortment 120 to 277 vac

14.0 WARRANTY

14.1 All systems are guaranteed to be free from material defects and workmanship for a
period 1 year following delivery.
14.2 Batteries are warranted for 15 years, pro-rated.

15.0 MAINTENANCE

15.1 Maintenance contracts provide start-up, training and required annual tests
and documentation in accordance with NFPA article 70.
 